Contactor,7,5kW/400V,DC-operated Partno. DILM17-10(RDC24) Articleno. 277018 Program Product range Contactors Application Contactors for Motors Subrange Contactors up to 170 A, 3 pole Connection technique Screw terminals Pole 3 pole Rated operational current AC-3 380 V 400 V Ie A 18 Ith =Ie A 40 220 V 230 V P kW 5 380 V 400 V P kW 7.5 660 V 690 V P kW 11 220 V 230 V P kW 2.5 380 V 400 V P kW 4.5 660 V 690 V P kW 6.5 AC-1 Conventional free air thermal current, 3 pole, 50 - 60 Hz Open at 40 C Max. rating for three-phase motors, 50 - 60 Hz AC-3 AC-4 Contacts N/O = Normally open 1 N/O Contact sequence Instructions Contacts to EN 50 012. integrated suppressor circuit in actuating electronics with mirror contact. Can be combined with auxiliary contact DILM32-XHI.. DILA-XHI(V).. DILM32-XHI11-S Voltage AC/DC DC operation Approbationen UL approval CSA approval Product Standards UL File No. UL CCN CSA File No. CSA Class No. NA Certification Specially designed for NA Yes Yes IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking E29096 NLDX 012528 2411-03, 3211-04 UL listed, CSA certified No General Standards IEC/EN 60947, VDE 0660, UL, CSA Lifespan, mechanical AC operated Operations x DC operated Operations x 02/17/2012 6 10 6 10 HPL-ED2011 V2.0 EN (UX111) 10 10 1 / 11 Operating frequency, mechanical AC operated Operations/ h 5000 DC operated Operations/ h 5000 Climatic proofing Ambient temperature Damp heat, constant to IEC 60068-2-78 Damp heat, cyclic to IEC 60068-2-30 C Open C - 25 - 60 Enclosed C - 25 - 40 Storage C - 40 - 80 g 10 N/O contact g 7 N/C contact g 5 g 6.9 N/O contact g 5.3 N/C contact g 3.5 Mounting position, AC- and DC operated Mechanical shock resistance (IEC/EN 60068-2-27) Half-sinusoidal shock, 10 ms Main contacts N/O contact Auxiliary contacts Mechanical shock resistance (IEC/EN 60068-2-27) when tabletopmounted Half-sinusoidal shock, 10 ms Main contacts N/O contact Auxiliary contacts Protection type IP00 Protection against direct contact when actuated from front (EN 90274) Finger- and back-of-hand proof Weight AC operated kg 0.42 DC operated kg 0.48 Terminal capacity main cable Solid mm 2 1 x (0.75 - 16) 2 x (0.75 - 10) Flexible with ferrule mm 2 1 x (0.75 - 16) 2 x (0.75 - 10) Stranded mm 2 1 x 16 Solid or stranded AWG 18 - 6 Main cable connection screw/bolt Tightening torque M5 Nm 3.2 Terminal capacity control circuit cables Solid mm 2 1 x (0.75 - 4) 2 x (0.75 - 4) Flexible with ferrule mm 2 1 x (0.75 - 1.5) 2 x (0.75 - 1.5) Solid or stranded AWG 18 - 14 Control circuit cable connection screw/bolt Tightening torque M3.5 Nm 1.2 Pozidriv screwdriver Size 2 Standard screwdriver mm 0.8 x 5.5 1x6 Tool Main cable 02/17/2012 HPL-ED2011 V2.0 EN (UX111) 2 / 11 Control circuit cables Pozidriv screwdriver Size 2 Standard screwdriver mm 0.8 x 5.5 1x6 Terminal capacity control circuit cables Solid mm 2 1 x (0.75 - 2.5) 2 x (0.75 - 2.5) Flexible mm 2 1 x (0.75 - 2.5) 2 x (0.75 - 2.5) Flexible with ferrule mm 2 1 x (0.75 - 1.5) 2 x (0.75 - 1.5) Solid or stranded AWG 18 - 14 Stripping length mm 10 Screwdriver blade width mm 3.5 Uimp V AC 8000 Rated insulation voltage Ui V AC 690 Rated operational voltage Ue V AC 690 between coil and contacts V AC 440 between the contacts V AC 440 A 238 220/230 V A 170 380/400 V A 170 500 V A 170 660/690 V A 120 Tool Mainconductingpaths Rated impulse withstand voltage Overvoltage category/pollution degree III/3 Safe isolation to VDE 0106 Part 101 and Part 101/A1 Making capacity (p.f. to IEC/EN 60947) Up to 690 V Breaking capacity Short-circuit rating Short-circuit protection maximum fuse Type "2" coordination 400 V gG/gL 500 V A 35 690 V gG/gL 690 V A 35 400 V gG/gL 500 V A 63 690 V gG/gL 690 V A 50 at 40 C Ith =Ie A 40 at 50 C Ith =Ie A 38 at 55 C Ith =Ie A 37 at 60 C Ith =Ie A 35 Ith A 32 open Ith A 88 enclosed Ith A 80 Type "1" coordination AC AC-1 duty Conventional free air thermal current, 3 pole, 50 - 60 Hz Open enclosed Conventional free air thermal current, 1 pole AC-3 duty 02/17/2012 HPL-ED2011 V2.0 EN (UX111) 3 / 11 Rated operational current AC-3 open, 50 - 60 Hz, 3 pole Ie 220/230 V Ie A 18 240 V Ie A 18 380/400 V Ie A 18 415 V Ie A 18 440V Ie A 18 500 V Ie A 18 660/690 V Ie A 12 Motor rating P kWh 220/230 V P kW 5 240V P kW 5.5 380/400 V P kW 7.5 415 V P kW 10 440 V P kW 10.5 500 V P kW 12 660/690 V P kW 11 AC-4 duty Rated operational current AC-4 open, 50 - 60 Hz, 3 pole Ie 220/230 V Ie A 10 240 V Ie A 10 380/400 V Ie A 10 415 V Ie A 10 440 V Ie A 10 500 V Ie A 10 8 660/690 V Ie A Motor rating P kWh 220/230 V P kW 2.5 240 V P kW 3 380/400 V P kW 4.5 415 V P kW 5 440 V P kW 5.5 500 V P kW 6 660/690 V P kW 6.5 60 V Ie A 35 110 V Ie A 35 220 V Ie A 35 440 V Ie A 2.9 60 V Ie A 35 110 V Ie A 35 220 V Ie A 10 440 V Ie A 0.6 60 V Ie A 35 110 V Ie A 35 220 V Ie A 10 440 V Ie A 0.6 Current heat loss at Ith W 7.3 Current heat loss at Ie to AC-3/400 V W 1.9 DC Rated operational current, open DC-1 operation DC-3 operation DC-5 operation Currentheatloss(3pole) 02/17/2012 HPL-ED2011 V2.0 EN (UX111) 4 / 11 Impedance per pole m Voltage tolerance x Uc Magnetsystems 2 AC operated Pick-up x Uc 0.8 - 1.1 Drop-out voltage AC operated Dropout x Uc 0.3 - 0.6 Notes RDC 24 (Umin 24 V DC/Umax 27 V DC) Example: Uc = 0.7 x Umin - 1.2 x Umax / Uc = 0.7 x 24 V - 1.2 x 27 V DC DC operated Pick-up x Uc Notes 0.7 - 1.2 at least smoothed two-phase bridge rectifier or three-phase rectifier DC operated Dropout x Uc 0.15 - 0.6 50 Hz Pick-up VA 52 50 Hz Sealing VA 7.1 50 Hz Sealing W 2.1 60 Hz Pick-up VA 67 60 Hz Sealing VA 8.7 60 Hz Sealing W 2.6 50/60 Hz Pick-up VA 62 58 50/60 Hz Sealing VA 9.1 6.5 50/60 Hz Sealing W 2.5 2 DC operated Pick-up W 12 DC operated Sealing W 0.5 % DF 100 Closing delay ms 16 - 22 Opening delay ms 8 - 14 Power consumption of the coil in a cold state and 1.0 x Uc Duty factor Switching times at 100 % Uc (approximate values) Main contacts AC operated DC operated ms Closing delay ms 47 Opening delay ms 30 ms 10 Arcing time Lifespan, mechanical; Coil 50/60 Hz at 50 Hz Mechanical lifespan at 50 Hz approx. 30% lower than under "Technical data, general" Electromagneticcompatibility(EMC) Emitted interference to EN 60947-1 Interference immunity to EN 60947-1 TechnicaldataaccordingtoETIM4.0 Number of main contacts as N/Os 3 Rated operation current Ie at AC-1, 400 V 40 Connection type main circuit Screw connection Rated control voltage Us at AC 60HZ V Number of auxiliary contacts as N/Os Rated control voltage Us at AC 50HZ 0 1 V 0 Number of auxiliary contacts as N/Cs 0 Suitable for rail-mounting No Rated control voltage Us at DC V Voltage type for actuation Rated operation current Ie at AC-3, 400 V DC A Number of N/Cs as main contact Motor rating at AC-3, 400 V 02/17/2012 27 18 0 kWh HPL-ED2011 V2.0 EN (UX111) 7.5 5 / 11 Characteristics 1: Overload relay 2: Suppressor 3: Auxiliary contact modules 02/17/2012 HPL-ED2011 V2.0 EN (UX111) 6 / 11 Squirrel-cage motor Operating characteristics Starting:from rest Stopping:after attaining full running speed Electrical characteristics Make: up to 6 x rated motor current Break: up to 1 x rated motor current Utilization category 100 % AC-3 Typical applications Compressors Lifts Mixers Pumps Escalators Agitators Fans Conveyor belts Centrifuges Hinged flaps Bucket-elevators Air conditioning system General drives in manufacturing and processing machines 02/17/2012 HPL-ED2011 V2.0 EN (UX111) 7 / 11 Extreme switching duty Squirrel-cage motor Operating characteristics Inching, plugging, reversing Electrical characteristics Make: up to 6 x rated motor current Break: up to 6 x rated motor current Utilization category 100 % AC-4 Typical applications Printing presses Wire-drawing machines Centrifuges Special drives for manufacturing and processing machines CAD-Data Product standards CAD data: http://eaton-moeller.partcommunity.com Dimensions 02/17/2012 HPL-ED2011 V2.0 EN (UX111) 8 / 11 Contactor with auxiliary contact module 02/17/2012 HPL-ED2011 V2.0 EN (UX111) 9 / 11 Lateral clearance to earthed parts: 6 mm Additionalproductinformation(links) IL03407014Z (IL03407014Z) Contactor 02/17/2012 ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL03407014Z2010_10.pdf HPL-ED2011 V2.0 EN (UX111) 10 / 11 Motor starters and "Special Purpose Ratings" for the North American market http://www.moeller.net/binary/ver_techpapers/ver953en.pdf Busbar Component Adapters for modern Industrial control panels http://www.moeller.net/binary/ver_techpapers/ver960en.pdf The Interaction of Contactors with PLCs http://www.moeller.net/binary/ver_techpapers/ver957en.pdf Standard Compliant and Functionally Safe Engineering Design with Mechanical Auxiliary Contacts http://www.moeller.net/binary/ver_techpapers/ver956en.pdf Switchgear for Luminaires http://www.moeller.net/binary/ver_techpapers/ver955en.pdf Effect of the Cabel Capacitance of Long Control Cables on the Actuation of Contactors http://www.moeller.net/binary/ver_techpapers/ver949en.pdf X-Start - Modern Switching Installations Efficiently Fitted and Wired Securely http://www.moeller.net/binary/ver_techpapers/ver938en.pdf Mirror Contacts for Highly-Reliable Information Relating to SafetyRelated Control Functions http://www.moeller.net/binary/ver_techpapers/ver944en.pdf X-Start - New Generation:100 years of Moeler contactors - Continous Progress- http://www.moeller.net/binary/ver_techpapers/ver937en.pdf Switchgear of Power Factor Correction Systems http://www.moeller.net/binary/ver_techpapers/ver934en.pdf 02/17/2012 Eaton Industries GmbH http://www.moeller.net/en (c) 07/2011 by Eaton Industries GmbH HPL-ED2011 V2.0 EN 11 / 11