02/17/2012 HPL-ED2011 V2.0 EN (UX111) 1 / 11
Contactor,7,5kW/400V,DC-operated
Part�no. DILM17-10(RDC24)
Article�no. 277018
Program
Product range Contactors
Application Contactors for Motors
Subrange Contactors up to 170 A, 3 pole
Connection technique Screw terminals
Pole 3 pole
Rated operational current
AC-3
380 V 400 V IeA 18
AC-1
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C Ith =IeA 40
Max. rating for three-phase motors, 50 - 60 Hz
AC-3
220 V 230 V P kW 5
380 V 400 V P kW 7.5
660 V 690 V P kW 11
AC-4
220 V 230 V P kW 2.5
380 V 400 V P kW 4.5
660 V 690 V P kW 6.5
Contacts
N/O = Normally open 1 N/O
Contact sequence
Instructions Contacts to EN 50012.
integrated suppressor circuit in actuating electronics
with mirror contact.
Can be combined with auxiliary contact DILM32-XHI..
DILA-XHI(V)..
DILM32-XHI11-S
Voltage AC/DC DC operation
Approbationen
UL approval Yes
CSA approval Yes
Product Standards IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking
UL File No. E29096
UL CCN NLDX
CSA File No. 012528
CSA Class No. 2411-03, 3211-04
NA Certification UL listed, CSA certified
Specially designed for NA No
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
AC operated Operations x
106
10
DC operated Operations x
106
10
02/17/2012 HPL-ED2011 V2.0 EN (UX111) 2 / 11
Operating frequency, mechanical
AC operated Operations/
h
5000
DC operated Operations/
h
5000
Climatic proofing Damp heat, constant to IEC 60068-2-78
Damp heat, cyclic to IEC 60068-2-30
Ambient temperature °C
Open °C - 25 - 60
Enclosed °C - 25 - 40
Storage °C - 40 - 80
Mounting position, AC- and DC operated
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact g 10
Auxiliary contacts
N/O contact g 7
N/C contact g 5
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-
mounted
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact g 6.9
Auxiliary contacts
N/O contact g 5.3
N/C contact g 3.5
Protection type IP00
Protection against direct contact when actuated from front (EN 90274) Finger- and back-of-hand proof
Weight
AC operated kg 0.42
DC operated kg 0.48
Terminal capacity main cable
Solid mm21 x (0.75 - 16)
2 x (0.75 - 10)
Flexible with ferrule mm21 x (0.75 - 16)
2 x (0.75 - 10)
Stranded mm21 x 16
Solid or stranded AWG 18 - 6
Main cable connection screw/bolt M5
Tightening torque Nm 3.2
Terminal capacity control circuit cables
Solid mm21 x (0.75 - 4)
2 x (0.75 - 4)
Flexible with ferrule mm21 x (0.75 - 1.5)
2 x (0.75 - 1.5)
Solid or stranded AWG 18 - 14
Control circuit cable connection screw/bolt M3.5
Tightening torque Nm 1.2
Tool
Main cable
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 x 5.5
1 x 6
02/17/2012 HPL-ED2011 V2.0 EN (UX111) 3 / 11
Control circuit cables
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 x 5.5
1 x 6
Terminal capacity control circuit cables
Solid mm21 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible mm21 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible with ferrule mm21 x (0.75 - 1.5)
2 x (0.75 - 1.5)
Solid or stranded AWG 18 - 14
Tool
Stripping length mm 10
Screwdriver blade width mm 3.5
Main�conducting�paths
Rated impulse withstand voltage Uimp V
AC
8000
Overvoltage category/pollution degree III/3
Rated insulation voltage UiV
AC
690
Rated operational voltage UeV
AC
690
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between coil and contacts V
AC
440
between the contacts V
AC
440
Making capacity (p.f. to IEC/EN 60947)
Up to
690 V
A 238
Breaking capacity
220/230 V A 170
380/400 V A 170
500 V A 170
660/690 V A 120
Short-circuit rating
Short-circuit protection maximum fuse
Type “2” coordination
400 V gG/gL
500 V
A 35
690 V gG/gL
690 V
A 35
Type “1” coordination
400 V gG/gL
500 V
A 63
690 V gG/gL
690 V
A 50
AC
AC-1 duty
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C Ith =IeA 40
at 50 °C Ith =IeA 38
at 55 °C Ith =IeA 37
at 60 °C Ith =IeA 35
enclosed Ith A 32
Conventional free air thermal current, 1 pole
open Ith A 88
enclosed Ith A 80
AC-3 duty
02/17/2012 HPL-ED2011 V2.0 EN (UX111) 4 / 11
Rated operational current AC-3 open, 50 - 60 Hz, 3 pole Ie
220/230 V IeA 18
240 V IeA 18
380/400 V IeA 18
415 V IeA 18
440V IeA 18
500 V IeA 18
660/690 V IeA 12
Motor rating P kWh
220/230 V P kW 5
240V P kW 5.5
380/400 V P kW 7.5
415 V P kW 10
440 V P kW 10.5
500 V P kW 12
660/690 V P kW 11
AC-4 duty
Rated operational current AC-4 open, 50 - 60 Hz, 3 pole Ie
220/230 V IeA 10
240 V IeA 10
380/400 V IeA 10
415 V IeA 10
440 V IeA 10
500 V IeA 10
660/690 V IeA 8
Motor rating P kWh
220/230 V P kW 2.5
240 V P kW 3
380/400 V P kW 4.5
415 V P kW 5
440 V P kW 5.5
500 V P kW 6
660/690 V P kW 6.5
DC
Rated operational current, open
DC-1 operation
60 V IeA 35
110 V IeA 35
220 V IeA 35
440 V IeA 2.9
DC-3 operation
60 V IeA 35
110 V IeA 35
220 V IeA 10
440 V IeA 0.6
DC-5 operation
60 V IeA 35
110 V IeA 35
220 V IeA 10
440 V IeA 0.6
Current�heat�loss�(3�pole)
Current heat loss at Ith W 7.3
Current heat loss at Ie to AC-3/400 V W 1.9
02/17/2012 HPL-ED2011 V2.0 EN (UX111) 5 / 11
Impedance per pole mΩ 2
Magnet�systems
Voltage tolerance x Uc
AC operated Pick-up x Uc0.8 - 1.1
Drop-out voltage AC operated Drop-
out
x Uc0.3 - 0.6
Notes RDC 24 (Umin 24 V DC/Umax 27 V DC)
Example: Uc = 0.7 x Umin - 1.2 x Umax / Uc = 0.7 x 24 V - 1.2 x 27 V DC
DC operated Pick-up x Uc0.7 - 1.2
Notes at least smoothed two-phase bridge rectifier or three-phase rectifier
DC operated Drop-
out
x Uc0.15 - 0.6
Power consumption of the coil in a cold state and 1.0 x Uc
50 Hz Pick-up VA 52
50 Hz Sealing VA 7.1
50 Hz Sealing W 2.1
60 Hz Pick-up VA 67
60 Hz Sealing VA 8.7
60 Hz Sealing W 2.6
50/60 Hz Pick-up VA 62
58
50/60 Hz Sealing VA 9.1
6.5
50/60 Hz Sealing W 2.5
2
DC operated Pick-up W 12
DC operated Sealing W 0.5
Duty factor %
DF
100
Switching times at 100 % Uc (approximate values)
Main contacts
AC operated
Closing delay ms 16 - 22
Opening delay ms 8 - 14
DC operated ms
Closing delay ms 47
Opening delay ms 30
Arcing time ms 10
Lifespan, mechanical; Coil 50/60 Hz at 50 Hz Mechanical lifespan at 50 Hz approx. 30% lower than under “Technical
data, general”
Electromagnetic�compatibility�(EMC)
Emitted interference to EN 60947-1
Interference immunity to EN 60947-1
Technical�data�according�to�ETIM�4.0
Number of main contacts as N/Os 3
Rated operation current Ie at AC-1, 400 V 40
Connection type main circuit Screw connection
Rated control voltage Us at AC 60HZ V 0
Number of auxiliary contacts as N/Os 1
Rated control voltage Us at AC 50HZ V 0
Number of auxiliary contacts as N/Cs 0
Suitable for rail-mounting No
Rated control voltage Us at DC V 27
Voltage type for actuation DC
Rated operation current Ie at AC-3, 400 V A 18
Number of N/Cs as main contact 0
Motor rating at AC-3, 400 V kWh 7.5
02/17/2012 HPL-ED2011 V2.0 EN (UX111) 6 / 11
Characteristics
1: Overload relay
2: Suppressor
3: Auxiliary contact modules
02/17/2012 HPL-ED2011 V2.0 EN (UX111) 7 / 11
Squirrel-cage motor
Operating characteristics
Starting:from rest
Stopping:after attaining full running speed
Electrical characteristics
Make: up to 6 x rated motor current
Break: up to 1 x rated motor current
Utilization category
100 % AC-3
Typical applications
Compressors
Lifts
Mixers
Pumps
Escalators
Agitators
Fans
Conveyor belts
Centrifuges
Hinged flaps
Bucket-elevators
Air conditioning system
General drives in manufacturing and processing machines
02/17/2012 HPL-ED2011 V2.0 EN (UX111) 8 / 11
Extreme switching duty
Squirrel-cage motor
Operating characteristics
Inching, plugging, reversing
Electrical characteristics
Make: up to 6 x rated motor current
Break: up to 6 x rated motor current
Utilization category
100 % AC-4
Typical applications
Printing presses
Wire-drawing machines
Centrifuges
Special drives for manufacturing and processing machines
CAD-Data
Product standards CAD data: http://eaton-moeller.partcommunity.com
Dimensions
02/17/2012 HPL-ED2011 V2.0 EN (UX111) 9 / 11
Contactor with auxiliary contact module
02/17/2012 HPL-ED2011 V2.0 EN (UX111) 10 / 11
Lateral clearance to earthed parts: 6 mm
Additional�product�information�(links)
IL03407014Z (IL03407014Z) Contactor ftp://ftp.moeller.net/DOCUMENTATION/AWA_INSTRUCTIONS/IL03407014Z2010_10.pdf
02/17/2012 Eaton Industries GmbH
http://www.moeller.net/en
© 07/2011 by Eaton Industries GmbH
HPL-ED2011 V2.0 EN
11 / 11
Motor starters and "Special Purpose Ratings" for the North American
market
http://www.moeller.net/binary/ver_techpapers/ver953en.pdf
Busbar Component Adapters for modern Industrial control panels http://www.moeller.net/binary/ver_techpapers/ver960en.pdf
The Interaction of Contactors with PLCs http://www.moeller.net/binary/ver_techpapers/ver957en.pdf
Standard Compliant and Functionally Safe Engineering Design with
Mechanical Auxiliary Contacts
http://www.moeller.net/binary/ver_techpapers/ver956en.pdf
Switchgear for Luminaires http://www.moeller.net/binary/ver_techpapers/ver955en.pdf
Effect of the Cabel Capacitance of Long Control Cables on the Actuation
of Contactors
http://www.moeller.net/binary/ver_techpapers/ver949en.pdf
X-Start - Modern Switching Installations Efficiently Fitted and Wired
Securely
http://www.moeller.net/binary/ver_techpapers/ver938en.pdf
Mirror Contacts for Highly-Reliable Information Relating to Safety-
Related Control Functions
http://www.moeller.net/binary/ver_techpapers/ver944en.pdf
X-Start - New Generation:100 years of Moeler contactors - Continous
Progress-
http://www.moeller.net/binary/ver_techpapers/ver937en.pdf
Switchgear of Power Factor Correction Systems http://www.moeller.net/binary/ver_techpapers/ver934en.pdf