02/17/2012 HPL-ED2011 V2.0 EN (UX111) 5 / 11
Impedance per pole mΩ 2
Magnet�systems
Voltage tolerance x Uc
AC operated Pick-up x Uc0.8 - 1.1
Drop-out voltage AC operated Drop-
out
x Uc0.3 - 0.6
Notes RDC 24 (Umin 24 V DC/Umax 27 V DC)
Example: Uc = 0.7 x Umin - 1.2 x Umax / Uc = 0.7 x 24 V - 1.2 x 27 V DC
DC operated Pick-up x Uc0.7 - 1.2
Notes at least smoothed two-phase bridge rectifier or three-phase rectifier
DC operated Drop-
out
x Uc0.15 - 0.6
Power consumption of the coil in a cold state and 1.0 x Uc
50 Hz Pick-up VA 52
50 Hz Sealing VA 7.1
50 Hz Sealing W 2.1
60 Hz Pick-up VA 67
60 Hz Sealing VA 8.7
60 Hz Sealing W 2.6
50/60 Hz Pick-up VA 62
58
50/60 Hz Sealing VA 9.1
6.5
50/60 Hz Sealing W 2.5
2
DC operated Pick-up W 12
DC operated Sealing W 0.5
Duty factor %
DF
100
Switching times at 100 % Uc (approximate values)
Main contacts
AC operated
Closing delay ms 16 - 22
Opening delay ms 8 - 14
DC operated ms
Closing delay ms 47
Opening delay ms 30
Arcing time ms 10
Lifespan, mechanical; Coil 50/60 Hz at 50 Hz Mechanical lifespan at 50 Hz approx. 30% lower than under “Technical
data, general”
Electromagnetic�compatibility�(EMC)
Emitted interference to EN 60947-1
Interference immunity to EN 60947-1
Technical�data�according�to�ETIM�4.0
Number of main contacts as N/Os 3
Rated operation current Ie at AC-1, 400 V 40
Connection type main circuit Screw connection
Rated control voltage Us at AC 60HZ V 0
Number of auxiliary contacts as N/Os 1
Rated control voltage Us at AC 50HZ V 0
Number of auxiliary contacts as N/Cs 0
Suitable for rail-mounting No
Rated control voltage Us at DC V 27
Voltage type for actuation DC
Rated operation current Ie at AC-3, 400 V A 18
Number of N/Cs as main contact 0
Motor rating at AC-3, 400 V kWh 7.5