Type: DILM40(230V50HZ,240V60HZ)
Article No.: 277766
Ordering information
Rated operational current AC−3 400 V IeA 40
Max. rating for three−phase motors, 50 – 60 Hz AC−3
230 V PkW 12.5
Max. rating for three−phase motors, 50 – 60 Hz AC−3
400 V PkW 18.5
Max. rating for three−phase motors, 50 – 60 Hz AC−3
690 V PkW 23
Max. rating for three−phase motors, 50 – 60 Hz AC−4
230 V PkW 5
Max. rating for three−phase motors, 50 – 60 Hz AC−4
400 V PkW 9
Max. rating for three−phase motors, 50 – 60 Hz AC−4
690 V PkW 12
Conventional thermal current I th = I e AC−1 Open Ith = IeA 50
For use with DILM150−XHI(V)..
DILM1000−XHI(V)..
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
AC operated Operations × 10610
DC operated Operations × 10610
Operating frequency, mechanical
AC operated Operations/h 5000
DC operated Operations/h 5000
Climatic proofing Damp heat, constant, to IEC 60068−2−78
Damp heat, cyclical, to IEC 60068−2−30
Ambient temperature
1
Open °C −25/60
Enclosed °C −25/40
Storage °C −40/80
Mechanical shock resistance (IEC/EN 60068−2−27)
Half−sinusoidal shock, 20 ms
Main contacts
Make contact g 10
Auxiliary contacts
Make contact g 7
Break contact g 5
Protection type IP00
Protection against direct contact when actuated from
front (IEC 536) Finger− and back−of−hand proof
Weight
AC operated kg 0,9
DC operated kg 1,1
Terminal capacity Main cable
Solid mm21 × (2.5 – 16)
2 × (2.5 – 16)
Flexible with ferrule mm22 × (2.5 – 25)
1 × (2.5 – 35)
Stranded mm21 × (16 – 50)
2 × (16 – 35)
Solid or stranded AWG 12 – 2
flat conductor
Number of
segments ×
width ×
thickness
mm 2 × (6 × 9 × 0.8)
Anschlussschraube Hauptleiter M6
Tightening torque Nm 3
Terminal capacity Control circuit cables
Solid mm21 × (0.75 – 4)
1 × (0.75 – 4)
Flexible with ferrule mm2 1 × (0.75 – 2.5)
2 × (0.75 – 2.5)
Solid or stranded AWG 18 – 14
Anschlussschraube Hilfsleiter M3.5
Tightening torque Nm 1.2
Tool
Main cable
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 × 5.5
1 × 6
Control circuit cables
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 × 5.5
1 × 6
Terminal capacity Control circuit cables
Solid mm20.75 – 2.5
2
Flexible mm20.75 – 2.5
Flexible with ferrule mm20.75 – 2.5
Solid or stranded AWG 18 – 14
Tool
Stripping length mm 10
Screwdriver blade width mm 3,5
Main conducting paths
Rated impulse withstand voltage Uimp V AC 8000
Overvoltage category/pollution degree III/3
Rated insulation voltage
AC UiV AC 690
Rated operational voltage UeV AC 690
Safe isolation to VDE 0106 Part 101 and Part 101/A1
between coil and contacts V AC 440
between the contacts V AC 440
Making capacity (cos Õ to IEC/EN 60947) up to 690
VA 560
Breaking capacity
220/230 V A 400
380/400 V A 400
500 V A 400
660/690 V A 250
Component lifespan
AC−3/AC−4  Tripping characteristics
Maximum operating frequency
AC−1; 400 V IeOps/h 800
AC−3; 400 V IeOps/h 800
AC−4; 400 V IeOps/h 300
Short−circuit rating
Short−circuit protection Maximum fuse
Type “2” coordination
400 V gG/gL 500 V A 63
690 V gG/gL 690 V A 50
Type “1” coordination
400 V gG/gL 500 V A 125
690 V gG/gL 690 V A 80
AC
AC−1 duty
conv. therm. current 3−pole 50 – 60 Hz
open
at 40 °C Ith A 60
at 50 °C Ith A 57
at 55 °C Ith A 55
at 60 °C Ith A 50
Enclosed Ith A 45
3
Conventional free air thermal current, 1−pole
open Ith A 125
Enclosed Ith A 112
AC−3 duty
Rated operational current AC−3 open, 50 – 60 Hz,
3−pole
220/230 V IeA 40
240 V IeA 40
380/400 V IeA 40
415 V IeA 40
440V IeA 40
500 V IeA 40
660/690 V IeA 25
Motor rating
220/230 V PkW 12,5
240V PkW 13,5
380/400 V PkW 18,5
415 V PkW 24
440 V PkW 25
500 V PkW 28
660/690 V PkW 23
AC−4 duty
Rated operational current AC−4 open, 50 – 60 Hz,
3−pole
220/230 V IeA 18
240 V IeA 18
380/400 V IeA 18
415 V IeA 18
440 V IeA 18
500 V IeA 18
660/690 V IeA 14
Motor rating
220/230 V PkW 5
240 V PkW 5,5
380/400 V PkW 9
415 V PkW 9,5
440 V PkW 10
500 V PkW 11
660/690 V PkW 12
DC
of three−phase capacitors open
DC−1 operation
60 V IeA 50
110 V IeA 50
220 V IeA 45
440 V IeA 2,9
DC−3 operation
4
60 V IeA 50
110 V IeA 50
220 V IeA 25
440 V IeA 0,6
DC−5 operation
60 V IeA 50
110 V IeA 50
220 V IeA 25
440 V IeA 0,6
Current heat loss (3−pole)
Current heat loss at Ith W 11,3
Current heat loss at Ie to AC−3/400 V W 7,2
Impedance per pole m& 1,5
Magnet systems
Voltage tolerance
AC operated
AC operated Pick−up × Uc0,8 – 1,1
Drop−out voltage AC operated
Drop−out voltage AC operated Abfall × Uc0,3 – 0,6
DC operated
DC operated Pick−up × Uc0,7 – 1,2
DC operated
DC operated Abfall × Uc0,15–0,6
Power consumption of the coil in a cold state and 1.0
× Uc
50 Hz Pick−up VA 130
50 Hz Pick−up W 80
50 Hz Sealing VA 14
50 Hz Sealing W 4
DC operated Pick−up W 24 at 24 V
DC operated Sealing W 0.5 at 24 V
Duty factor % DF 100
Switching times at 100 % Uc (approximate values)
Main contacts
AC operated
Closing delay ms 25
Opening delay ms 25
DC operated
Closing delay ms 60
Opening delay ms 20
Arcing time ms 10
Electromagnetic compatibility (EMC)
Emitted interference to EN 60947−1
Interference immunity to EN 60947−1
Mounting position, AC− and DC operated
5
Moeller GmbH, Hein−Moeller−Str. 7−11, D−53115 Bonn
E−Mail: catalog@moeller.net, Internet: www.moeller.net, http://catalog.moeller.net
Copyright 2005 by Moeller GmbH. Subject to modifications. HPL−C2005GB−INT V3.0