Alternate Operation Relay
61F-AN/-APN2
Increases Motor Life and Enables Operating
Only One Pump When Cleaning Tanks or as
an Emergency Measure for Pump Failures.
Electronic Relay with the same operation as the G4Q Latching
Relay. Compared with the G4Q, the 61F-AN/-APN2 has a
shorter power supply application time and no restrictions on
mounting direction.
Compact Models (61F-AN) and Compact Plug-in Models (61F-
APN2) available.
Note: A changeover switch must be included in the sequence to enable
operating only one pump.
Refer to Safety Precautions for Floatless Level
Controllers.
Ordering Information
Note: When ordering, specify the desired operating voltage at the end of the model number.
Specifications
Ratings
* Hold-down clip PFC-N8 is attached only 61F-APN2.
Contact Ratings (with G2RK Keep Relay)
Characteristics
Type Model
Alternate Operation
Relay
61F-AN
61F-APN2
Supply voltage 100, 110, 200, 220 VAC; 50/60 Hz
Operating voltage range 85% to 110% of rated voltage
Power consumption 3 VA
Accessories Hold-down clip PFC-N8 *
Example: 61F-AN [220VAC]
Desired supply voltage
Item Resistive load (cosφ = 1) Inductive load (cosφ = 0.4, L/R = 7 ms)
Max. load 3 A at 250 VAC 1.5 A at 250 VAC
Carry contact 3 A
Max. operating current 3 A
Max. switching capacity 750 VA 375 VA
Response time Operate: 25 ms max.
Release: 30 ms max.
Minimum pulse width Min. ON time: 40 ms min.
Min. OFF time: 200 ms min.
Insulation resistance 100 MΩ min. at 500 VDC (between each terminal and power supply)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between each terminal and power supply)
Vibration resistance 10 to 55 Hz, 1-mm double amplitude
Shock resistance 10 G (approx. 98 m/s2)
Life expectancy Mechanical: 1,000,000 operations (at operating frequency of 1,800 operations/hour)
Electrical: 100,000 operations min.
(rated load)
Ambient temperature Operating: –10 to 55°C
Ambient humidity Operating: 45% to 85% RH
Weight 61F-AN: Approx. 215 g
61F-APN2: Approx. 190 g
61F-AN/-APN2
2
Time Chart for Alternate Operation of Water Supply
When the 61F-A@ Alternate Operation Relay is combined with a
Floatless Level Switch, the Relay output contacts switch (break)
while the contactor is engaged. The Relay output contacts will not
switch simultaneously with engaging the contactor. In other words,
the contactor or other load is switched with the output contacts from
the Floatless Level Switch, not directly with the output contacts from
the 61F-A@ Alternate Operation Relay. Using water supply as an
example, after the control level is reached and the 61F Controllers’
NC contacts turn OFF (break), the Relay’s output contacts switch.
The next time the 61F Controller’s NC contacts turn ON, the output
contacts have already switched. Thus, only the continuous carry
current needs to be considered for the load capacity of the 61F-
APN2, enabling application to the rated carry current of 3 A.
61F-AN (Compact Model)
Used in combination with a 61F-G@N Floatless Level Switch.
Operation
The 61F-AN is used in combination with a Floatless Level Switch
for alternate operation when using two pumps for level control in
one location.
When power is applied to the input terminals S0 and S2, NO
contacts Tc1 and Ta1, and NO contacts Ta2 and Tc2 are turned ON
via the alternate operation control circuit and the output circuit. This
state is held with a magnetic lock even if the power supply is turned
OFF.
When power is applied to the input terminals again, the NO
contacts are turned OFF and the NC contacts Tc1 and Tb1 and NC
contacts Ta2 and Tc2 are turned ON. This state is held with a
magnetic lock even if the power supply is turned OFF.
The above operation is repeated each time the power supply is
turned ON.
(Power Supply Pulse Response Method) Connections (Refer to connection diagram.)
61F-APN2 (Compact Plug-in Model)
Used in combination with a Floatless Level Switch.
Operation
The 61F-APN2 is used in combination with a Floatless Level Switch
for alternate operation when using two pumps for level control in
one location.
When power is applied to the input terminals 2 and 7, NO contacts
1 and 3, and NO contacts 6 and 8 are turned ON via the alternate
operation control circuit and the output circuit. This state is held
with a magnetic lock even if the power supply is turned OFF.
When power is applied to the input terminals again, the NO
contacts are turned OFF and the NC contacts 1 and 4 and NC
contacts 5 and 8 are turned ON. This state is held with a magnetic
lock even if the power supply is turned OFF.
The above operation is repeated each time the power supply is
turned ON.
(Power Supply Pulse Response Method)
Note: Refer to Connecting Sockets, Mounting Brackets, DIN Rails for
the applicable Sockets.
Ta
Tb
Power
Output
Tc1-Ta1
61F
61F-AN,
-APN2
Output
Tc1-Tb1
Contactor 1
Contactor 2
Xc2
Xc1
X
Power circuit
Alternate operation
control circuit
Output circuit
G2RK
(61F-AN)
(See note.)
Tb1
Tc1
Ta 1
Tb2
Tc2
Ta 2
S0
S2
Note: The above diagram is for a rated voltage of 200 or 220 VAC.
Power is supplied to S0 and S1 for 100 or 110 VAC.
Xc2
Xc14
3
1
5
6
8
X
2
7
Power circuit
Alternate operation
control circuit
Output circuit
G2RK
(61F-APN2)
61F-AN/-APN2
3
Connections (Refer to connection diagram.)
Connect output terminal Ta in the 61F-G example (page 5) to input
terminal 2 on the 61F-APN2.
Connect coil terminal A on each of the two contactors to the
switching contact terminals 3 and 4 on the 61F-APN2.
Use the switching contact terminals 5 and 6 on the 61F-APN2 to
control the operation of the two pumps.
The power supply of the 61F-APN2 is 100, 110, 200, or 220 VAC.
Be sure to use the correct power supply.
Output contact between
1-3 and 6-8
Output contact between
1-4 and 5-8
Power supply voltage
between 2-7
200 ms min.40 ms min.
61F-AN/-APN2
4
Connections
Combining with the 61F-GN
61F-AN
Dimensions:
page 17
Combining with the 61F-GN
Water supply source
MCCB
RS
M1
T
Commercial
voltage 220 VAC
61F-AN
61F-GN
(See note.)
S2
S0
T
a1
T
c1
T
b1
T
a1
T
c1
T
b1
L2
L1
To p ower
source T
X
M2
Contactor 2
Contactor 1
P1
A
A
P2
Output
circuit
Alternate
operation
control circuit
PS-3S
E1
E2
E3
S1
S2
S0
T
b
T
c
T
a
E
3
E
2
E
1
8 V
UU
24 V
61F-11N
Relay Unit
Transformer
U
0 V
110 V
220 V
The relay operation can be monitored if indicators are
connected as shown by the dotted line.
Water
tank
Power
circuit
Motor
protec-
tion relay
Motor
protection
relay
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Water Supply
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Drainage
61F-AN/-APN2
5
Combining with the 61F-G
61F-APN2
Dimensions:
page 17
Combining with the 61F-G
MCCB
RST
Commercial voltage
220 VAC
61F-G
(See note.)
T
b
T
c
T
a
E
2
S
2
S
1
S
0
E
3
E
1
8 V
U
U
U
24 V
0 V
110 V
220 V
61F-11
Relay Unit
2187
345
L
1
6
L
2
To p ower source T
61F-APN2
Water supply source
M1 M2
Contactor 2
Contactor 1
P1 P2
PS-3S
E
1
E
2
E
3
The relay operation can be monitored
if indicators are connected as shown
by the dotted line.
Electronic
circuit
Water
tank
Motor
protec-
tion relay
Motor
protection
relay
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Connection Sockets
PF083A (Front-connecting)
PL08 (Rear-connecting)
Water Supply
MCCB
RST
Commercial voltage
220 VAC
61F-G
(See note.)
T
b
T
c
T
a
E
2
S
2
S
1
S
0
E
3
E
1
8 V
U
U
U
24 V
0 V
110 V
220 V
61F-11
Relay Unit
2187
345
L
1
6
L
2
To p ower source T
61F-APN2
Wastewater tank
Reservoir
M1
M2
Contactor 2
Contactor 1
P1 P2
E
2
E
3
PS-3S
E
1
The relay operation can be monitored
if indicators are connected as shown
by the dotted line.
Electronic
circuit
Motor
protection
relay
Motor
protec-
tion relay
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Connection Sockets
PF083A (Front-connecting)
PL08 (Rear-connecting)
Drainage
61F-AN/-APN2
6
Combining with the 61F-G1N
61F-AN
Dimensions:
page 17
Combining with the 61F-G1N
Water supply source
MCCB
RS
M1
T
Commercial voltage
220 VAC
61F-G1N
61F-AN
(See note.)
Alarm
S0
S1
S2
E1
E2
E3
E1'
E2'
Tc2
Tb2
Ta1
Tb1
S2
S0
Ta1
Tc1
Tb1
T
a2
Tc2
Tb2
L2
L1
X
P1
Contactor 1
M2
P2
Output
circuit
Alternate
operation
control circuit
PS-3S
PS-3S
E1
E2
E3
E2'
E3
E1'
B
Transformer
8 V
U
1
(E
4
)
U
1
U
2
U
2
U
2
U
1
24 V
24 V
0 V
110 V
220 V
61F-11N
Relay Unit
61F-11N
Relay Unit
The relay operation can be monitored if indicators are
connected as shown by the dotted line.
Power
circuit
Contactor
2
Water
tank
To power
source T
Motor
protection
relay
Motor
protection
relay
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Water Supply
The 61F-G1N is to be used only for supplying water and cannot be used for alternate operation for controlling drainage.
Drainage
61F-AN/-APN2
7
Combining with the 61F-G1
61F-APN2
Dimensions:
page 17
Combining with the 61F-G1
Water supply source
MCCB
RS
M1
T
Commercial voltage
220 VAC
(See
note.)
P1
Contactor 1
M2 P2
PS-3S
E1
E2
E3
E2'
E3
E1'
61F-G1
S0Tb1Ta1 Tc2 Tb2
S1S2
2187
3
L1L2
456
E3E2E1E2'E1'(E4)
220 V
110 V
0 V24 V
24 V
To power source T
61F-APN2
B
U1
U1
U1
U2
U2
U2
8 V
61F-11
Relay Unit
61F-11
Relay Unit
The relay operation can be monitored if indicators are
connected as shown by the dotted line.
Electronic
circuit
Alarm
Contactor
2
Water
tank
Motor
protection
relay
Motor
protection
relay
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Water Supply
The 61F-G1N is to be used only for supplying water and cannot be used for alternate operation for controlling drainage.
Water Drainage
61F-AN/-APN2
8
Combining with the 61F-G2N
61F-AN
Dimensions:
page 17
Combining with the 61F-G2N
Water supply source
MCCB
RS
M1
T
Commercial voltage
220 VAC
61F-G2N
61F-AN
(See note.)
S0
S1
S2
E1
E2
E3
E4
S2
S0
T
a1
T
a2
T
c2
T
a1
T
c1
T
b1
T
c1
T
b1
T
a1
T
c1
T
b1
L2
L1
X
M2
Contactor 2Contactor 1
P1 P2
Output
circuit
Alternate
operation
control circuit
Transformer
8 V
U
1
U
2
U
1
U
2
24 V
24 V
0 V
110 V
220 V
Alarm
61F-11N
Relay Unit
U
2
B
PS-4S
E4
E2
E3
E1
The relay operation can be monitored if indicators are
connected as shown by the dotted line.
Power
circuit
61F-11N
Relay Unit
Water
tank
To p ower
source T
Motor
protec-
tion relay
Motor
protection
relay
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Water Supply
Wastewater tank
MCCB
RS
M1
T
Commercial voltage
220 VAC
61F-G2N
61F-AN
(See
note.)
S
0
S
1
S
2
E
1
E
2
E
3
E
4
S
2
S
0
T
a1
T
a2
T
c2
T
a1
T
c1
T
b1
T
c1
T
b1
T
a1
T
c1
T
b1
L
2
L
1
X
M2
Contactor 1
P1 P2
Output
circuit
Alternate
operation
control circuit
PS-4S
E
4
E
2
E
3
E
1
Transformer
8 V
U
1
U
2
U
1
U
2
24 V
24 V
0 V
110 V
220 V
Alarm
61F-11N
Relay Unit
U
2
B
The relay operation can be monitored if indicators are
connected as shown by the dotted line.
Power
circuit
61F-11N
Relay Unit
Contac-
tor 2
To p ower
source T
Motor
protec-
tion relay
Motor
protection
relay
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Drainage
61F-AN/-APN2
9
Combining with the 61F-G2
61F-APN2
Dimensions:
page 17
Combining with the 61F-G2
Water supply source
MCCB
RS
M1
T
Commercial voltage
220 VAC
M2
Contactor 2
Contactor 1
P1 P2
PS-4S
E
4
E
2
E
3
E
1
61F-G2
(See note.)
S
2
E
3
E
2
E
4
E
1
S
1
S
0
8 V
U
2
U
2
U
1
U
1
U
2
24 V
24 V
0 V
110 V
220 V
61F-11
Relay Unit
B
21
8
7
3
4
5
L
1
6
L
2
To p ower source T
61F-APN2
T
a1
T
c1
T
b1
T
a2
T
c2
The relay operation can be monitored
if indicators are connected as shown
by the dotted line.
Electronic
circuit
61F-11
Relay Unit
Alarm
Water
tank
Motor
protection
relay
Motor
protection
relay
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Water Supply
Wastewater tank
MCCB
RS
M1
T
Commercial voltage
220 VAC
M2
Contactor 2Contactor 1
P1
P2
PS-4S
E4
E2
E3
E1
61F-G2
(See note.)
S2E3E2E4E1
S1
S0
8 V
U
2
U
2
U
1
U
1
U
2
24 V
24 V
0 V
110 V
220 V
B
Alarm
218
7
345
L1
6
L2
To p ower source T
61F-APN2
T
a1
T
c1
T
b1
T
a2
T
c2
The relay operation can be monitored
if indicators are connected as shown
by the dotted line.
Electronic
circuit
61F-11
Relay Unit
61F-11
Relay Unit
Motor
protection
relay
Motor
protection
relay
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Drainage
61F-AN/-APN2
10
Combining with the 61F-G3N
61F-AN
Dimensions:
page 17
Combining with the 61F-G3N
Water supply source
MCCB
RS
M1
T
Commercial voltage
220 VAC
61F-G3N
61F-AN
(See note.)
S0
Ta
Tc
Tb
B1
B2
S1
S2
LH
Lc
LL
E1
E2
E3
E4
E5
PL
B
PL
S2
S0
T
a1
T
c1
T
b1
T
a1
T
c1
T
b1
L2
L1
Power supply
X
M2
Contactor 1
Contactor
2
P1 P2
Output
circuit
Alternate
operation
control circuit
PS-5S
E1
E2
E3
E4
E5
Transformer
8 V
U
3
U
1
U
3
U
1
U
2
U
2
U
1
U
2
U
3
Lamp
Lamp
Alarm Bell
24 V
24 V
0 V
110 V
220 V
61F-11N
Relay Unit
To 61F-11N
Relay Unit
The relay operation can be monitored if indicators are
connected as shown by the dotted line.
To p ower
source T
Power
circuit
61F-11N
Relay Unit
61F-11N
Relay Unit
Upper
limit
Lower
limit
Motor
protection
relay
Motor
protection
relay
Water
tank
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Water Supply
Wastewater tank
Reservoir
MCCB
RS
M1
T
61F-G3N
61F-AN
(See note.)
S0
Ta
Tc
Tb
B1
B2
S1
S2
LH
Lc
LL
E1
E2
E3
E4
E5
PL
B
PL
S2
S0
T
a1
T
c1
T
b1
T
a1
T
c1
T
b1
L2
L1
X
P1
Contactor
2
Contactor 1
M2 P2
Output
circuit
Alternate
operation
control circuit
Transformer
8 V
U
3
U
1
U
3
U
1
U
2
U
2
U
1
U
2
U
3
Lamp
Lamp
Alarm Bell
24 V
24 V
0 V
110 V
220 V
E1
E2
E3
E4
E5
PS-5S
Commercial voltage
220 VAC
The relay operation can be monitored if indicators are
connected as shown by the dotted line.
Power
circuit
To p ower
source T
To 61F-11N
Relay Unit
61F-11N
Relay Unit
61F-11N
Relay Unit
61F-11N
Relay Unit
Power supply
Upper
limit
Lower
limit
Motor
protection
relay
Motor
protection
relay
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Drainage
61F-AN/-APN2
11
Combining with the 61F-G3
61F-APN2
Dimensions:
page 17
Combining with the 61F-G3
Water supply source
MCCB
RS
M1
T
Commercial voltage
220 VAC 61F-G3
(See note.)
S1
TcTbB1E1LcB2E3
S2E2LLLH E4
S0
PL
TaE5
P1
Contactor
2
Contactor 1
M2 P2
PS-5S
E1
E2
E3
E4
E5
8 V
U2U2
U1
U1
U3U3
U1
U2
Lamp
24 V
24 V
0 V
110 V
220 V
U3
24 V
PL
Lamp
B
218
7
345
L1
6
L2
To p o wer source T
61F-APN2
The relay operation
can be monitored if
indicators are
connected as shown
by the dotted line.
Electronic
circuit
61F-11N
Relay Unit
61F-11N
Relay Unit
61F-11N
Relay Unit
Alarm
Bell
Power
supply
Upper
limit
Lower
limit
Motor
protection
relay
Motor
protection
relay
Water
tank
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Water Supply
Wastewater tank
Reservoir
MCCB
RS
M1
T
61F-G3
S1
TcTbB1E1LcB2E3
S2E2LLLH E4
S0
PL
TaE5
P1 M2 P2
8 V
U
2
U
2
U
1
U
1
U
3
U
3
U
1
U
2
Lamp
24 V
24 V
0 V
110 V
220 V
U
3
24 V
PL
Lamp
B
2187
345
L1
6
L2
61F-APN2
E1
E2
E3
E4
E5
PS-5S
Commercial voltage
220 VAC
To p o wer source T
The relay operation
can be monitored if
indicators are
connected as shown
by the dotted line. 61F-11N
Relay Unit
61F-11N
Relay Unit
61F-11N
Relay Unit
Electronic
circuit
(See
note.)
Alarm
Bell
Power
supply
Upper
limit
Lower
limit
Contactor
2
Contactor 1
Motor
protection
relay
Motor
protection
relay
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Drainage
61F-AN/-APN2
12
Combining with the 61F-G4N
Alternate Operation Relay
61F-AN
Dimensions:
page 17
Combining with the 61F-G4N
Contactor 1
Water supply source
MCCB
RS
M1
T
Commercial
voltage 220 VAC
61F-G4N
61F-AN
PS-5S
PS-4S
E1
BL
1
BH
2
BL
2
LH
1
LL
1
LL
2
LH
2
Tc
Tc2
B
TA
S0
S1
S2
BH
1
BL
1
BH
2
BL
2
LH
1
LL
1
LL
2
LH
2
BH
1
E4
E8
E2
E1
E3
E5
E6
E7
E8
(See note.)
S
2
S
0
T
a1
T
c1
T
b1
T
a2
T
c2
T
b2
T
a2
T
b2
61F-11N
Relay Unit
61F-11N
Relay Unit
61F-11N
Relay Unit
61F-11N
Relay Unit
61F-11N
Relay Unit
220 V
U4
U3
U2
U5
U2
U4
U5
U1
U1
U3
U5
U2
X
U4
U1
U3
X
X
110 V
MY3 Relay
0 V
Transformer
8 V
24 V
24 V
X
X
P1
Contactor 2
M2 P2
Output
circuit
Alternate
operation
control circuit
E4
E5
E2
E7
E8
E6
E3
E8
The relay operation can be monitored if indicators are
connected as shown by the dotted line.
To power
source T
Power
circuit
To 61F-11N
Relay Unit
Elevated tank
repletion
Water supply
source upper
limit
Water supply
source lower
limit
Elevated tank
water
shortage
Elevated tank
repletion
Water supply
source upper
limit
Water supply
source lower
limit
Elevated tank
water
shortage
Motor
protection
relay
Motor
protection
relay
Water
tank
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Water Supply
The 61F-G4N is to be used only for supplying water and cannot be used alternately for controlling drainage.
Drainage
61F-AN/-APN2
13
Combining with the 61F-G4
Alternate Operation Relay
61F-APN2
Dimensions:
page 17
Combining with the 61F-G4
61F-G4
U
2
U
3
U
2
U
5
U
1
U
2
U
3
U
4
MK3P
Relay
U
4
XU
5
U
1
XU
3
U
4
XU
1
U
5
LL
1
21
87
345
L
1
6
L
2
LL
2
LH
1
X
LH
2
BL
1
BL
2
BH
1
BH
2
LL
1
LL
2
LH
1
LH
2
BL
1
BL
2
BH
1
BH
2
E
4
E
3
E
2
E
1
S
0
S
1
S
2
T
C
T
C2
BTAE
8
E
7
E
6
E
5
200 V
100 V
0 V
24 V
24 V
220 V
110 V
0 V24 V
24 V
24 V
Electronic
circuit
Contactor 1
Water supply source
MCCB
RS
M1
T
To power source T
61F-APN2
PS-5S
PS-4S
E
4
E
1
(See note.)
P1
Contactor 2
M2 P2
8 V
61F-1
Relay Unit
61F-1
Relay Unit
61F-1
Relay Unit
61F-1
Relay Unit
61F-1
Relay Unit
E
7
E
8
E
2
E
3
E
8
E
5
E
6
Commercial
voltage 220 VAC
Elevated
tank water
shortage
Elevated
tank
repletion
Water
supply
source
lower limit
Water
supply
source
upper limit
Elevated
tank water
shortage
Elevated
tank
repletion
Water
supply
source
lower limit
Water
supply
source
upper limit
Motor
protection
relay
Motor
protection
relay
Water
tank
Note: Be sure to ground the common Electrode E3 (the longest Electrode).
Water Supply
The 61F-G4N is to be used only for supplying water and cannot be used alternately for controlling drainage.
Drainage
61F-AN/-APN2
14
At 220 VAC
Water Supply (When Combined with 61F-G1P)
*Be sure to ground terminal 15.
P1
Power
source
220 VAC
R S T
Water supply source
M1
Electromagnetic switch 1
43
56
12
87
L
1
L
2
Water
tank
Electronic
circuit
61F-APN2
For example, operation indication is
possible by the connection as
shown by the dotted line.
P2M2
E
2
E
3
E
1
Control circuit
Control circuit
E
3
E
2
E
1
24 V
24 V
0 V
220 V8 V
Alarm
89 15 111 2
Pushbutton switch
Electromagnetic
switch 2
AA
Knife
switch
14 12 345
U
2
U
1
B
U
1
61F-G1P
76
10
U
1
U
2
U
2
*
THR THR
PS-3S
PS-3S
61F-AN/-APN2
15
Water Supply (When Combined with 61F-GP-N)
*Be sure to ground terminal 4.
P1
E2
E3
E1
Knife
switch
Power
source
220 VAC
R S T
0 V
220 V
8 V
24 VControl circuit
U
M2 P2
Water supply source
M1
435
6
12
87
L1
L2
10 11 1 2
Water tank
61F-GP-N
Electronic
circuit
61F-APN
For example, operation indication is
possible by the connection as
shown by the dotted line.
Electromagnetic switch 1 Electromagnetic switch 2
AA
93
8
U
6
7
4
5
Water supply source
*
THR THR PS-3S
U
61F-AN/-APN2
16
Water Drainage (When Combined with 61F-G2P)
*Be sure to ground terminal 15.
P1
Power
source
220 VAC
R S T
Water supply source
M1
Electromagnetic switch 1
4356
1287
L1L2
Electronic
circuit
61F-ANP2
Knife
switch
For example, operation indication is
possible by the connection as shown
by the dotted line.
P2M2
E1
E3
E4
Control circuit
24 V
24 V
0 V
220 V8 V
Alarm
815 10 119 1
E2
AA
14 6127
2
43
U1
U2
61F-G2P
U1
U2
U2
5
B
*
Control circuit
THR THR
PS-4S
Electromag-
netic switch 2
61F-AN/-APN2
17
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Safety Precautions
Refer to Safety Precautions for All Level Controllers.
5
3
5
100 70
10 5
40
4
50
11
50
65
54
35.4
4 min.
3.4
10
4 min.
90
39
56
9Twelve, M3.5 sems screws
Terminal cover
32
60 11
1414
25
42
(See note.)
61F-AN
Note: Dimensions are with the DIN rail mounting (sliding) bracket attached.
49.4
3870
84
61F-APN2
PF083A
91
61F-APN2 Use a PFC-N8 Mounting Bracket to mount the Level
Controller to a PF083A Rail-mounted Socket.
PFC-N8
Note: PFC-N8 Mounting Bracket (provided with
the Level Controller)
83
4
4.5
t = 0.3
6
Approx.
80
$/7(51$7(23(5$7,215(/$<
6285&(9$&
FREQ.:50/60 Hz
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omrons sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omrons analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyers application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyers application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2014.10
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2014 All Right Reserved.